Technical FAQs

Ask a Question

Why Vijeo Citect fails to communicate to Fuji Electric Paperless recorder over modnet and shows error "channel offline " in kernel.

Vijeo Citect can communicate to Fuji Electric recorder provided that Modbus Station Address or Modbus Node address is set and used together with IP address .
Failing to use Node address with IP adderss will give error as "Chanel offline " and Vijeo Citect will fail to communicate with it.
Refer Fuji Electric recorder manual to identify or set Station Address as shown below:-


Make sure to use this Station Address with IP address in IOdevice form.




 
Was this helpful?
What can we do to improve the information ?