What are the constraints to use the motor starter Tesys "U" instead of conventional Control products?

Kindly be informed that the Motor Starter Tesys "U" Can be used under the following Conditions:

1- Act for DOL starting Method

2- Used for motors up to 15 KW only 

if the two above conditions are not valid, in this case the conventional type 1 and type 2 coordination starting methods are to be used 