Can PM1200 able to reach more than 13.88 monthes for the energy integrator overflow ?

According to the last information mentioned in 2015 catalouge as attached 

If you select the max load condition then it will go up to 13.88 months.
 
For eg if you consider max load i.e.1000 KVA as per table given in the user guide then with the formula it is coming 13.88 months ,
            
(Max reading/ Power ratio)    = ( (9999 *10^6)/(1000*10^3)) = 9999
                                     ÷   24      =   416.625 days
                                     ÷   30      =   13.88 Months
                              
And the Example  given in the user manual it is 200KVA for that kind load it will store for a 5.78 years.
 
Below mentioned feature is available in PM1200 from Firmware version 03.05.00 Onwards for the overflow of energy.
 
1. Wh - setting resets all integ parameters when either Wh reaches 9999 GWh or Run hours reaches 9999 hours. Whichever occurs first, that triggers the reset.
OR
2. VAh E - setting resets all integ parameters when VAh reaches 9999 GVAh
OR
3. Wh E - setting resets all integ parameters when Wh reaches 9999 GWh
OR
4. VAh - setting resets all integ parameters when VAh reaches 9999 GVAh or Run hours reaches 9999 hours. Whichever occurs first, that triggers the reset.
 
Was this helpful?