Can refrence 29450 be used as an early-break auxiliary contact CAO for compact NSX ?

No reference 29450 is not used for this purpose. For Compact NSX100~250, the early-break (1 contact) and early-make (2 contact) contacts are LV429345 and LV429346 respectively. For Compact NSX400~630, the early-break (1 contact) and early-make (2 contacts) contacts are LV432605 and LV429346 respectively.