Technical FAQs

Ask a Question

What is the consumption of motorization used in RM6?

Motor consumption for RM6:
For DC operation: 240W.
For AC operation: 280VA.

Motor operation time for one-time closing operation:
For CIT mechanism: maximum 2sec.
For CI1 mechanism: maximum 13sec.

Note: for power supply sizing, you have to consider also that at least a 20A power supply is necessary to account for the motor's starting current.