Technical FAQs

Ask a Question

can we replace the existing 16A circuit breaker installed in 150mm high withdrawable bucket type cubicle of Blokset Switchboard with 100A circuit breaker.

It will not fit and we will need to get 4 Modules drawer (200mm) instead of 3 Modules (150mm). Please refer to the attached extract from the Blokset Technical Guide.
Was this helpful?
What can we do to improve the information ?