What is the maximum fuse rated current in SM6?

Maximum fuse rated current to be installed in fuse-switch combinations (QM cubicle) can be given as follows: 
- For SM6 up to 24kV: 200A* 
- For SM6 36kV: 63A*

*Please refer to attached pages showing fuse selection for transformer protection using QM as fuse rated current depends on transformer characteristics and network (nominal) voltage.
 