What is the Restricted earth fault protection and how to implement on Low Voltage

The restricted earth fault protection (ANSI 64REF) can be applied if the downstream power system neutral is earthed at the transformer (document attached).
This is a differential protection function that detects the difference between residual currents measured at the neutral earthing point and at the three-phase output of the transformer.
Please find attached document describing how to implement the estricted earth fault protection  with Masterpact Micrologic 6.0