Is it possible to disable the Long time protection in Micrologic for NS/NT/NW breakers?

The Long time protection can be disabled by changing the long-time rating plug if existing or to order "LT rating plug "Off",or sometime called without long-time protection reference 33545.
Please note that in this case :
*Ir = In for the short-time protection setting
*Frequency protection not available
*Load shedding / reconnection based on current not available  