How to resolve OFS Factory server 3.61 momentarily open and close with error 0x80080005 ?

Its being observed after installing and trying to open the OFS OPC server 3.61  bundled with Citect 2018, OPC factory will open momentarily and then close.
The error 0x80080005 is found in the event viewer indicating that the OPC server hasn’t registered with DCOM in a time.
This error  occurs when installed on Windows 10 & Windows Server 2008 R2.

To solve ensure directory  (C:\temp) exist in computer, if not create the same.