Is it possible to use TeSys GV2 and TeSys GV3 Range MPCB in DC applications?
The TeSys GV2 and TeSys GV3 range MPCB can be used in DC applications as per their technical specifications. Refer the below wiring connection for...
What is the function of battery used in Micrologic Trip unit.
The battery inside the Micrologic keeps the Clock and Calendar maintained when the Control Supply has failed. This battery also allows the testing...
What is the new tag point count licensing in Citect SCADA V7.0 ?
In CitectSCADA 6.10 or earlier, multiple tags that share the same I/O device address will be counted as a single I/O point. This is calculated at...
Is it possible to use Altivar 71 Drive for control of the Synchronous Motor.
Yes, Altivar 71 Drive can be used for control of the Synchronous Motor.  Note:   1. The Drive should be programmed for Open-Loop Control.   2. De-rate...
What is the maximum motor cable length allowed between the Sinus Filter and Altivar 71 Drive.
The maximum motor cable length allowed between the Sinus Filter and Altivar 71 Drive is 1000 Meters.
What is the accuracy of the Premium PLC CPU real time clock.
Real time clock accuracy: Accuracy of the real time clock is one second (%SW50) +/- 200ms. Resolution of the real time clock is one second (%SW50)...
Which are the latest GSD file revisions for ProfibusDP communication board of the Altivar 71 Drive.
The latest GSD File revisions required for ProfibusDP communication board of the Altivar 71 Drive are as follows:  1. The correct revision of GSD...
Do Unity Pro and Unity Application Generator (UAG) have separate licenses.
Yes, Unity Pro and UAG have separate licenses.   During installation of UAG, it detects the existing Unity Pro versions on your PC/Laptop and it will...
What is the execution time and memory consumption of the PIDFF instruction in Unity Pro Quantum platform.
It has been observed that the maximum time taken for executing PIDFF instruction is around 50 microseconds on Unity Pro Quantum platform.   Regarding...
What is the minimum rating of the Motor that can be used with the Altivar 31/61/71 Range of Drives.
The motor current should not be less than 0.2 times the nominal Drive current when the motor is driven by Altivar 31/61/71 Drives, for thermal protection....